WORKING PRINCIPAL OF MIX BED DEIONISER IN D.M PLANT:-

Mixed Bed Deionizer is very important water treatment equipment for any industries for treated boiler water. Mix bed deionizer or mixed bed polisher are typically installed where water quality is less then 1 micro ohm conductivity is required.  Mix Bed Deionizer is a single shell unit and contain with strongly acid cation and strongly basic anion mixed with proper ratio . mixed bed shell contain strong acid cation (SAC) resin and strong base Anion (SAB) resin combined to a ratio of approximately 40% cation resin and strong base Anion (SBA) resin. Mixed bed  deionizer  is used to polish water at higher purity level it has been initially treated by either a two-be deionizer or a reverse osmosis unit.

After passing water through cation and anion exchangers water interned into mix bed unit where both of resin available when water is passing through it effluent water get contact with thasound of cation/anion exchangers resulting good quality of water in output. Internally resin bed contains a rubber lining inside where a good space for resin expansion when back wash is conducted through it.
In addition to the usual distributors, a mixed bed is fitted with a centre distribution and collection system. When backwash is conducted through mix bed unit the heaviest cation resin settled down and lighter anion resin are lift up.

After some time when back wash is stopped the resins settle without upsetting the separation. There is a well defined interface between the cation and anion resin bed and that interface is just at the level of center distributors.

Passing a solution of sodium Hydroxides ( caustic Soda ) then regeneration the anion resin and passing a solution of hydrochloric Acid regenerate the cation resin. Then the columns are rinsed individually and finally remixed again, by passing of 5 psi. Thus the unit become ready for another cycle of operation to produced pure Deionized water of electrical conductivity less then 0.5 us/cm equivalent to approximately 0.5 ppm of dissolved solids in D.M water. Reaction taking place in a mixed bed unit are similar to that of taking place in cation & anion exchanger.

 

“MAY ALSO LIKE THIS “

*INTRODUCTION AND WORKING PRINCIPAL OF REVERSE OSMOSIS

*Boiler Water analysis and it’s importance

*WATER IMPURITIES AND THEIR CLASSIFICATION

*Water impurities and their harmful effects on boiler

*Filtration process in water treatment

*Sedimentation Process in water treatment

*WORKING PRINCIPAL OF MIX BED DEIONISER IN D.M PLANT

General reaction taking place in cation exchanger

R-H+CaCo3→HCO3+R-Ca

General reaction taking place during regeneration of cation exchanger is :-
R-Ca +HCL→CaCl2+R-H

general reaction take place in anion exchanger

R-OH+HCO3→H-OH+R-CO3

general reaction taking place during regeneration of anion exchanger is

R-CO3 +NaOH →Na2Co3+R-OH

Hence the final composition of water after mix bed is
H+OH→H2O
(De-mieralized water )

Defect ,causes and remedies for mixed bed operation

Defect :- mixed bed quality not good

Causes: –
– resin not separated during backwash properly.
– air mix not properly.
– final rinse not proper
– some valves may be leakage & contaminated the treated water.
Remedies:-
– give extended backwash
– repeat the process
– repeat the process
– check & examine

Defect :– unit rinse takes long time

Causes :- –
– flow rate too low
– unit exhausted
– backwash valve passing
– anion resin originally fouled
– mixed bed air mixes not satisfactory
– Acid/ alkali pockets formation in unit

Remedies :-

– Increase flow rate
_ regeneration unit check and rectify.

Defect :- resin being lost
Causes :-
-Excessive backwash pressure
-Faulty collecting system
-Inlet strainer damaged

Remedies:-
– check inlets pressure and reduced if necessary

– examine it for breakage
Check and replaced

 

IF YOU LIKE THIS POST ” WORKING PRINCIPAL OF MIX BED DEIONISER IN D.M PLANT” PLEASE LIKE , SHARE AND YOU COMMENTS IS VERY VALUABLE SO PLEASE GIVE YOUR SUGGESTIONS IN COMMENT BOX please read once time if any mistake you find in this artical please suggest me through comment box or if  this website contains all original article which are written by me if any article on this site find copyrighted please inform me through at joginder005@gmail.com……..THANK’S

Facebook Comments
No Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

ION EXCHANGER IN WATER TREATMENT PROCESS (2)
D.M PLANT
1
ION EXCHANGER IN WATER TREATMENT PROCESS

ION EXCHANGER IN WATER TREATMENT PROCESS Today we discussed about an very important equipment which is used into the D.M plant into a power unit that’s equipment is ion-exchanger which is used for treating the boiler water .Ion-exchange or water conditioners one of the simplest methods now these days for removing …

INTRODUCTION AND WORKING PRINCIPAL OF REVERSE OSMOSIS
D.M PLANT
2
INTRODUCTION AND WORKING PRINCIPAL OF REVERSE OSMOSIS

INTRODUCTION AND WORKING PRINCIPAL OF REVERSE OSMOSIS Today we discussed about the reverse osmosis system in water purification system . now these days Water is an important resource for Industrial development. With increased automation and technological development, more stringent quality of water is specified and required. This has led to …

boiler watre analysis and requriement
D.M PLANT
Boiler Water analysis and it’s importance

Boiler Water analysis and it’s importance Water analysis The process of determining how much of various substances (impurities) are present in given sample of water is known as Water Analysis. Boiler water analysis is very important things in any power plant industries because of maintaining life of boiler or its …

Translate »